Place of Origin:
China
Brand Name:
Anges/SZAGS
Certification:
CE/ISO9001
Model Number:
AGS-150WDH
Model | AGS-150ADH | |
| nominal cooling capacity | kcal/h | 404200 |
| kw | 470 | |
| input power | kw | 162 |
| max running current | A | 370.1 |
| power supply | 3PH 380V 50Hz | |
| refrigerant | type | R407C |
| refrigerating circuit | 2 | |
| weight(kg) | 106 | |
| type of control | thermostatic expansion valve | |
| compressor | type | semi-hermetic screw |
| power(kw) | 67.7×2 | |
| quantity | 2 | |
| start-up mode | Y-△ | |
| capacity control | 0-25-50-75-100 | |
| condenser | type | air cooled high-efficient inner threaded copper-tubing aluminum fin type |
| cooling air flow (m3/h) | 155000 | |
| power(kw) | 27 | |
| evaporator | type | shell and tube |
| quantity | 2 | |
| chilled fluid flow (m3/h) | 80.8 | |
| inlet and outlet pipe diameter (inch) | 5" | |
| safety protection | compressor over temperature protection, over load protection, high and low pressure protection, flow switch protection, reversed and lacking phase protection, anti-freezing protection. | |
| dimension | Length(mm) | 3400 |
| Width(mm) | 4000 | |
| Height(mm) | 2053 | |
| net weight | kg | 4200 |
| running weight | kg | 4430 |
Note: 1. Nominal cooling capacity is according to:
Inlet chilled fluid temperature: 17℃
Outlet chilled fluid temperature: 12℃
Inlet cooling air temperature: 35℃
Outlet cooling air temperature: 45℃
2. Working Range:
The temperature range of chilled fluid is from 5℃ to 35℃;
Temperature difference between inlet and outlet chilled fluid is from 3℃ to 8℃.
Temperature difference between inlet and outlet cooling air is from 8℃ to 12℃.
The machine can be used while the ambient temperature is below 40℃.
We reserve the right to modify the above dimensions or parameters without further notice.