Contact Us

  • Product Name:

Address: No.23 Limin Road, Gangtou Village, Bantian, Longgang District, Shenzhen, P.R. of China

ZipCode: 518129

Tel : 86-755-28227245/28227244/2827242

Fax: 86-755-28227243/89582800

Email: anges@agschiller.com


 
New Products

Friend Link :

You are here: Home >> Product List >> Water-cooled-screw-chiller >> water cooled screw type chiller ( AGS-W )

water cooled screw type chiller ( AGS-W )

Product Categories: Water cooled screw chiller
addToBasket

send inquiry

Company Profile Tel :86-755-28227245/28227244/2827242 Fax:86-755-28227243/89582800

Product Description:

Introduction of water cooled screw type chiller unit
1.ANGES adopts world famous brand compressor--bitzer and hanbell which efficiency is 20% to 30% higher than those common ones.
2.Capacity control can apply to four step,three step and stepless control system;
3.High efficiency,low noise and small vibration;
4.R22,R134a,R407c can be chosen to meet your demand;
Technical data of AGS-W series from AGS-40WSH ~AGS-120WSH

Model

AGS-040WSH

AGS-050WSH

AGS-060WSH

AGS-075WSH

AGS-085WSH

AGS-100WSH

AGS-120WSH

Item

nominal cooling capacity

kcal/h

103200

133300

150500

202100

232200

253700

318200

kw

120

155

175

235

270

295

370

input power

kw

30

36

41

56

61

70

85

max. running current

A

71

84

96

131

142

188

200

power supply

3PH~380V 50HZ

refrigerant

type

R22 /R407c

refrigerating circuit

1

type of control

thermostatic expansion valve

compressor

type

semi-hermetic screw

quantity

1

start-up mode

Y- △

capacity control

0-25-50-75-100

condenser

type

shell and tube

evaporator

type

shell and tube

quantity

1

chilled fluid flow(m 3 /h)

21

27

30

40

46

51

64

safety protection

compressor over temperature, unit overload, high and low pressure, flow switch, phase sequence, phase-missing, antifreezing

net weight

kg

1400

1600

1800

2050

2250

2500

3200

running weight

kg

1600

1800

2000

2350

2550

2850

3600

Note: 1. nominal cooling capacity is according to:

Inlet chilled fluid temperature: 12℃.Outlet chilled fluid temperature: 7℃.

Inlet cooling water temperature: 30℃.Outlet cooling water temperature: 35℃.

2. working range:

The temperature range of chilled fluid is from 5℃ to 20℃;
Temperature difference between inlet and outlet chilled fluid is from 3℃ to 8℃.
The temperature range of cooling water is from 22℃ to 35℃;

Temperature difference between inlet and outlet cooling water is from 3℃ to 8℃.

We reserve the right to modify the above dimensions or parameters without further notice.