Company Profile Tel :86-755-28227245/28227244/2827242 Fax:86-755-28227243/89582800
ANGES HB series chiller is researched and developed to fully meet the demands of the modern international market , as it is no harm to the environment and has low energy consumption.
HBW Serials parameters
Item model
HBW-15(D)
HBW-20(D)
HBW-25(D)
HBW-30(D)
HBW-40(D)
HBW-50(D)
nominal cooling capacity
Kcal/h
38081
49553
57138
79120
103200
127280
50HZ/60HZ
45700
59464
68566
94600
123840
152736
Btu/h
151105
196626
226724
313948
409498
505047
50HZ/60HZ
181338
235953
272070
375373
491397
606056
KW
44.28
57.62
66.44
92
120
148
50HZ/60HZ
53.14
69.14
79.72
110
144
177.6
US.RT/h
12.59
16.39
18.89
26.16
34.13
42.09
50HZ/60HZ
15.11
19.66
22.67
31.28
40.95
50.51
input power
KW
15
19.5
22.4
29.4
38.4
47
power supply
3PH~380V50HZ (60HZ)
refrigerant
type
R407C
type of control
thermostatic expansion valve
compressor
type
hermetic scroll (piston)
power (KW)
6.75*2
9*2
10.1*2
13.6*2
17.7*2
22*2
condenser
type
shell and tube
cooling water flow (m3/h)
9.14
11.89
13.71
20.5
26.7
33
10.96
14.27
16.45
22.7
29.7
36.6
inlet and outlet pipe diameter
2"
2"
2-1/2"
3"
3"
3"
evaporator
type
water tank with coil (shell and tube)
chilled fluid flow (m3/h)
7.61
9.91
11.43
15.8
20.6
25.5
9.14
11.89
13.7
18.9
24.8
30.5
tank volume (L)
330
330
350
450
580
620
inlet and outlet pipe diameter
2"
2"
2-1/2"
2-1/2"
2-1/2"
3"
water pump
power (KW)
1.5
1.5
2.2
2.2
3
3
lift (m)
25
25
28
28
28
28
safety protection
compressor over temperature, over current, high and low pressure, over temperature,flow switch, phase sequence, phase-missing, exhaust overheating, antifreezing
dimension
length (mm)
1650
1650
1880
1880
2000
2000
width (mm)
710
710
710
910
980
980
height (mm)
1800
1880
1880
1800
1960
1960
weight
Kg
735
820
900
1150
1200
1500
Note: 1. nominal cooling capacity is according to:
Inlet chilled fluid temperature: 12℃.
Outlet chilled fluid temperature:7℃.
Inlet cooling water temperature: 25℃.
Outlet cooling water temperature:30℃.
2. working Range:
The temperature range of chilled fluid is from 5℃ to 35℃;
Temperature difference between inlet and outlet chilled fluid is from 3℃ to 8℃.
The temperature range of cooling water is from 18℃ to 35℃;
Temperature difference between inlet and outlet cooling water is from 3.5℃ to 10℃.