Technical parameters of air cooled refrigeration system

                                                  model                      Item
AC-1
AC-2
AC-3
AC-5
AC-6
AC-8(D)
nominal cooling capacity
Kcal/h
2382
4541
6803
11094
13091
17604
50HZ/60HZ
2786
5315
7955
13235
15901
21001
KW
2.77
5.28
7.91
12.9
15.22
20.47
50HZ/60HZ
3.24
6.18
9.25
15.39
18.49
24.42
US.RT/h
0.79
1.51
2.25
3.67
4.33
5.83
50HZ/60HZ
0.93
1.76
2.63
4.38
5.26
6.95
input power
KW
1.34
2.27
3.33
5.8
6.33
9.25
power supply
1PH~220V/50HZ (60HZ)
3PH~380V 50HZ (60HZ)
refrigerant
type
R22
type of control
capillary
compressor
type
hermetic rotary
hermetic scroll (piston)
power (KW)
0.89
1.77
2.8
4.66
5.2
3.8*2
condenser
type
finned copper tube + low noise outer rotor fan
evaporator
type
water tank with coil(shell and tube)
chilled fluid flow (m3/h)
0.476
0.908
1.36
2.22
2.6
3.52
0.557
1.063
1.59
2.65
3.2
4.2
 tank volume (L)
20
40
50
70
70
120
water pump
power (KW)
0.37
0.37
0.37
0.75
0.75
0.75
lift (m)
20
20
20
20
20
22
safety protection
compressor over temperature, over current, high and low pressure, over temperature,flow switch, phase sequence, phase-missing, exhaust overheating, antifreezing
dimension
length (mm)
500
580
930
1140
1140
1300
width (mm)
500
550
520
560
560
720
height (mm)
725
925
975
1040
1040
1350
weight
Kg
73
100
135
175
180
320
Note: 1. nominal cooling capacity is according to:
             Inlet chilled fluid temperature: 12℃
             Outlet chilled fluid temperature: 7℃
             Inlet cooling air temperature: 30℃                                                              
             Outlet cooling air temperature:35℃                                                                        
      2. working range:
             The temperature range of chilled fluid is from 5℃ to 35℃;
             Temperature difference between inlet and outlet chilled fluid is from 3℃ to 8℃.    
             It is better to use the chiller while the ambient temperature at or below 35℃.                           
We reserve the right to modify the above dimensions or parameters without further notice.      
 