Friend Link :

You are here: Home >> Product List >> Air-cooled-industrial-water-chiller >> Air cooled industrial chiller 30kw

Air cooled industrial chiller 30kw

addToBasket

send inquiry

Company Profile Tel :86-755-28227245/28227244/2827242 Fax:86-755-28227243/89582800

Product Description:

Air cooled industrial chiller
Model: AC-10(D)
Features:
High efficiency
Accurate temperature control ±1°C
Hitachi scroll type compressor
Error alarm for fault indication and Error code showed for checking the problem easily
Campact and elegant european design with Intelligent Digital Contral, easy for operation
Easy to install and maintain
One year warranty
Application
X-ray diffraction spectrometer
Wire cut / Spark erosion EDM (EDM=- Electron Discharge Machining)
Medical equipment
Machine tool
Induction hardening machine
High frequency welding machine
Hydraulic press
Pressure die casting
Furnaces
Power generators
Condenser cooling for low temperature test chambers
Injection moulding machine
Plasma spray / Coating machine
After coolers for compressed air drier
Chemical process plants
Dies & pigment manufacturing
Pharmaceutical industry
Electroplating plants
Anodizing plants
Food & beverage industry
Technical data

                                             Model
Item
AC-10(D)
nominal cooling capacity
kcal/h
22188
kw
25.8
input power
kw
10.37
power supply
3PH~380V/50HZ
refrigerant
type
R22
compressor
type
hermetic scroll
power(kw)
4.66*2
Cooling fan
cooling air flow(m3/h)
10000
evaporator
chilled fluid flow(m3/h)
4.44
inlet and outlet pipe diameter(inch)
1-1/2
pump
power(kw)
0.75
lift(m)
20
weight
kg
450
dimension
mm
1530*780*1470

Note:
1. Nominal cooling capacity is according to:
Inlet chilled fluid temperature: 12℃
Outlet chilled fluid temperature: 7℃
Inlet cooling air temperature: 30℃
Outlet cooling air temperature: 35℃
2. Working range:
The temperature range of chilled fluid is from 5℃ to 35℃;
Temperature difference between inlet and outlet chilled fluid is from 3℃ to 8℃.
It is better to use the chiller while the ambient temperature at or below 35℃.